GFR 4000 Features

• 10 mA - 3.0 adjustable trip level
• 10 Ohms - 100 KOhms adjustable trip
   for off-line insulation resistance
• Adjustable time delay 0 - 1.0 S
• Dual metering output
• Dual input power supply ac 24/120V
• Harmonic filtering

The GFR 4000 integrates two sensing functions to provide complete and continuous on and off-line sensitive ground fault protection for ac, 50-60 Hz fixed or portable equipment. The unit has both protective and predictive capabilities which provide a very high degree of network protection and increase personnel safety as well as minimizing risk of fire. The GFR 4000 can operate on single and three phase grounded, and resistance grounded power systems.

On-Line Leakage Current Sensing Operation
The GFR 4000 protects operators and equipment from dangerous leakage currents that may occur when a circuit is energized. The device has harmonic filtering to prevent nuisance tripping and a pick-up response time of <25mS.

Off-Line Insulation Resistance Monitoring Operation
The GFR 4000 will continue to monitor for ground faults once the circuit has been de-energized. When the circuit is off, the GFR 4000 changes state by means of a small auxiliary contact (110V/NC) on the main contactor to connect terminals 27 and 28. The GFR 4000 checks for off-line faults by determing resistance values on the circuit. The unit sends a small dc current onto the system which travels through the motor windings and interconnecting cable from the motor starter.

CT600 Series Current Transformers
The Weldsafe 4000 operates together with a CT600 series current transformer. There are different sizes available ranging from 1” to 8” depending upon the size of the load conductors passing through window.  Only the load carrying conductors pass through the C.T.. The ground wire must remain outside the C.T. core. It is also important that the cables passing through the C.T. be as straight as possible to minimize the possibility of core saturation.

Do you have a ground fault application?

We can help.

Contact us by phone or fax: 972-370-0664


Available Options

• Non-adjustable single trip level for ground fault
• Non-adjustable time, pick-up response <25 mS
• Monitoring up to ac1200 Hz
• Alternate insulation resistance trip values

Legend
H1           LED green POWER ON
H2           LED red GROUND FAULT
H3           LED red CT FAULT
H4           LED green off-line function ON ("active")
H5           LED red low INSULATION FAULT

K1           Insulation resistance monitor alarm relay
K2           Leakage current alarm relay

S1           Internal test button
S2           Internal reset button
S3           Leakage current selector switch
S4           Leakage current time delay selector
S6           External test button
S7           External reset button

R1           Insulation resistance potentiometer

Terminals
2                    Line connection for insulation resistance monitoring function
5-6                 ac 120 V input power supply (+/- 15%)
5-7                 ac 24 V input power supply (+/- 15%)
10-11-12        Contact for K1 alarm relay - insulation resistance
13-14-15        Contact for K2 alarm relay - leakage current
16-17             CT connection
18-19             Link for auto reset K2
19-20             Link for active mode K2
21-22             Link for auto reset K1
22-23             Link for active mode K1
24-25             Leakage current meter
25-26             Insulation resistance meter
27-28             Link for active mode for insulation resistance monitor
30                  Ground connection